In the study of heat transfer, critical heat flux (CHF) is the heat flux at which boiling ceases to be an effective form of transferring heat from a solid surface to a liquid.
Description
Boiling systems are those in which liquid coolant absorbs energy from a heated solid surface and undergoes a change in phase. In flow boiling systems, the saturated fluid progresses through a series of flow regimes as vapor quality is increased. In systems that utilize boiling, the heat transfer rate is significantly higher than if the fluid were a single phase (i.e. all liquid or all vapor). The more efficient heat transfer from the heated surface is due to heat of vaporization and sensible heat. Therefore, boiling heat transfer has played an important role in industrial heat transfer processes such as macroscopic heat transfer exchangers in nuclear and fossil power plants, and in microscopic heat transfer devices such as heat pipes and microchannels for cooling electronic chips.
The use of boiling as a means of heat removal is limited by a condition called critical heat flux (CHF). The most serious problem that can occur around CHF is that the temperature of the heated surface may increase dramatically due to significant reduction in heat transfer. In industrial applications such as electronics cooling or instrumentation in space, the sudden increase in temperature may possibly compromise the integrity of the device.
Two-phase heat transfer
The convective heat transfer between a uniformly heated wall and the working fluid is described by Newton's law of cooling:
where represents the heat flux, represents the proportionally constant called the heat transfer coefficient, represents the wall temperature and represents the fluid temperature. If decreases significantly due to the occurrence of the CHF condition, will increase for fixed and while will decrease for fixed .
Modes of CHF
The understanding of CHF phenomenon and an accurate prediction of the CHF condition are important for safe and economic design of many heat transfer units including nuclear reactors, fossil fuel boilers, fusion reactors, electronic chips, etc. Therefore, the phenomenon has been investigated extensively over the world since Nukiyama first characterized it.[1] In 1950 Kutateladze suggested the hydrodynamical theory of the burnout crisis.[2] Much of significant work has been done during the last decades with the development of water-cooled nuclear reactors. Now many aspects of the phenomenon are well understood and several reliable prediction models are available for conditions of common interests.
The use of the term critical heat flux (CHF) is inconsistent among authors.[3] The United States Nuclear Regulatory Commission has suggested using the term “critical boiling transition” (CBT) to indicate the phenomenon associated with a significant reduction in two-phase heat transfer.[4] For a single species, the liquid phase generally has considerably better heat transfer properties than the vapor phase, namely thermal conductivity. So in general CBT is the result of some degree of liquid deficiency to a local position along a heated surface. The two mechanisms that result in reaching CBT are: departure from nucleate boiling (DNB) and liquid film dryout.
DNB
Departure from nucleate boiling (DNB) occurs in sub-cooled flows and bubbly flow regimes. DNB happens when many bubbles near the heated surface coalesce and impede the ability of local liquid to reach the surface. The mass of vapor between the heated surface and local liquid is may be referred to as a vapor blanket.
Dryout
Dryout means the disappearance of liquid on the heat transfer surface which results in the CBT. Dryout of liquid film occurs in annular flow.[3] Annular flow is characterized by a vapor core, liquid film on the wall, and liquid droplets entrained within the core. Shear at the liquid-vapor interface drives the flow of the liquid film along the heated surface. In general, the two-phase HTC increases as the liquid-film thickness decreases. The process has been shown to occur over many instances of dryout events, which span a finite duration and local to a position.[3] The CBT occurs when the fraction of time a local position is subjected to dryout becomes significant.[3] A single dryout event, or even several dryout events may be followed by periods of sustained the liquid film in contact with the previously dry region . Many dryout events (hundreds or thousands) occurring in sequence are the mechanism for significant reduction in heat transfer associated dryout CBT.[3]
Post-CHF
Post-CHF is used to denote the general heat transfer deterioration in flow boiling process, and liquid could be in the form of dispersed spray of droplets, continuous liquid core, or transition between the former two cases. Post-dryout can be specifically used to denote the heat transfer deterioration in the condition when liquid is only in the form of dispersed droplets, and denote the other cases by the term Post-DNB. [5]
Correlations
The critical heat flux is an important point on the boiling curve and it may be desirable to operate a boiling process near this point. However, one could become cautious of dissipating heat in excess of this amount. Zuber,[6] through a hydrodynamic stability analysis of the problem has developed an expression to approximate this point.
Units: critical flux: kW/m2; hfg: kJ/kg; σ: N/m; ρ: kg/m3; g: m/s2.
It is independent of the surface material and is weakly dependent upon the heated surface geometry described by the constant C. For large horizontal cylinders, spheres and large finite heated surfaces, the value of the Zuber constant . For large horizontal plates, a value of is more suitable.
The critical heat flux depends strongly on pressure. At low pressures (including atmospheric pressure), the pressure dependence is mainly through the change in vapor density leading to an increase in the critical heat flux with pressure. However, as pressures approach the critical pressure, both the surface tension and the heat of vaporization converge to zero, making them the dominant sources of pressure dependency.[7]
For water at 1 atm, the above equation calculates a critical heat flux of approximately 1000 kW/m2.
See also
References
- ↑ Nukiyama, S. (1934). "Film boiling water on thin wires". Soc. Mech. Engng., Japan. 37.
- ↑ Kutateladze, S.S. (1950). "Hydromechanical model of the crisis of boiling under conditions of free convection". Journal of Technical Physics, USSR. 20 (11): 1389–1392.
- 1 2 3 4 5 Morse, R. W.; Moreira, T. A.; Chan, J.; Dressler, K. M.; Ribatski, G.; Hurlburt, E. T.; McCarroll, L. L.; Nellis, G. F.; Berson, A. (2021-10-01). "Critical heat flux and the dryout of liquid film in vertical two-phase annular flow". International Journal of Heat and Mass Transfer. 177: 121487. doi:10.1016/j.ijheatmasstransfer.2021.121487. ISSN 0017-9310.
- ↑ "Nuclear Regulatory Commission issuances. Volume 47, Number 3". 1998-03-01.
{{cite journal}}
: Cite journal requires|journal=
(help) - ↑ Yu, D., Feuerstein, F., Koeckert, L., & Cheng, X. (2018). Analysis and modeling of post-dryout heat transfer in upward vertical flow. Annals of Nuclear Energy, 115, 186-194.
- ↑ Zuber, Novak (June 1959). "Hydrodynamic aspects of boiling heat transfer". doi:10.2172/4175511. hdl:2027/mdp.39015086433532. Retrieved 4 April 2016.
{{cite journal}}
: Cite journal requires|journal=
(help) - ↑ "Fundamentals of Heat and Mass Transfer 6th Edition by Incropera".
{{cite journal}}
: Cite journal requires|journal=
(help)