Woolwich Power Station | |
---|---|
Country | England |
Location | Greenwich, London |
Coordinates | 51°29′40″N 0°03′57″E / 51.494400°N 0.065700°E |
Status | Decommissioned and demolished |
Construction began | 1891 |
Commission date | 1893 |
Decommission date | 1978 |
Owner(s) | As operator |
Operator(s) | Woolwich District Electric Lighting Company (1893–1903) Woolwich Borough Council (1903–1948) British Electricity Authority (1948–1955) Central Electricity Authority (1955–1957) Central Electricity Generating Board (1958–1978) |
Thermal power station | |
Primary fuel | Coal |
Site area | 7.5 acres |
Chimneys | 3 |
Cooling towers | None |
Cooling source | River water |
Power generation | |
Units operational | 1 × 12.5 MW, 3 × 34.5 MW, 2 × 30 MW (in 1957) |
Make and model | Fraser & Chalmers/GEC |
Units decommissioned | All |
Nameplate capacity | See table in text |
Annual net output | See graph in text |
External links | |
Commons | Related media on Commons |
grid reference TQ434792 |
Woolwich Power Station was a coal-fired power station on the south bank of the Thames at Woolwich.
History
The first station was opened at the site in 1893 by the Woolwich District Electric Lighting Company adapted from boat repair shops,[1] and subsequently taken over by the Metropolitan Borough of Woolwich. During later construction work in 1912 the timbers of a Tudor warship believed to be Henry VII's 1488 ship Sovereign were uncovered on the site.[2]
The station was redeveloped in the 1920s and again in the 1940s and 1950s, ultimately having three fluted brick chimneys on the east side of the station. It occupied a site of just over seven and a half acres.
In 1906 alternating current and direct current was being supplied generated by a 2.5 MW machine supplied by C.A. Parsons Ltd.[3] Between 1912 and 1917 additional plant was installed ranging from 1.5 MW to 6 MW capacity.[3] The generating capacity, maximum load, and electricity generated and sold was as follows:[4]
Year | Generating capacity, MW | Maximum load, MW | Electricity generated, GWh | Electricity sold, GWh |
1903/4 | 1.458 | 0.733 | 0.763 | 0.695 |
1912/3 | 1.750 | 1.610 | 3.504 | 2.939 |
1918/9 | 12.51 | 8.615 | 28.142 | 25.416 |
1919/20 | 12.51 | 6.979 | 14.574 | 12.537 |
1923/4 | 20.25 | 10.550 | 29.107 | 23.600 |
1936/7 | 40.00 | 40.74 | 90.261 (134.0 purchased) | 125.024 |
The coal used by the station was usually shipped from the Yorkshire and Northumberland areas and offloaded by crane onto a deep trough conveyor. At its peak the station was burning over 1000 tons of coal a day.[5]
Redevelopment
The earliest buildings on the site were replaced in 1924–28. The 1924–28 station known as the low-pressure section had four Babcock & Wilcox boilers (decommissioned 1963) and 1 × 12.5 MW Fraser & Chalmers/GEC turbo-alternator which generated at 6.6 kV.[3] The 1940–48 intermediate-pressure section had six Babcock & Wilcox boilers and 3 × 34.5 MW Fraser & Chalmers/GEC turbo-alternators generating at 22 kV. The final 1952–57 high-pressure section had four John Thompson ‘La Mont’ boilers and 2 × 30 MW Fraser & Chalmers/GEC turbo-alternators generating at 22 kV.[3]
The steam conditions at the turbine stop-valves of the various steam systems were:[6]
Pressure | Temperature | |
---|---|---|
Low pressure | 190 psi (13 bar) | 316 °C |
Intermediate pressure | 400 psi (27.6 bar) | 427 °C |
High pressure | 600 psi (41.4 bar) | 454 °C |
The total steam generating capacity from 1966 to 1974 was 1,710,000 lb/hr (215.4 kg/s); then 92.0 kg/s during 1975–78.[6]
One of the high-pressure 30 MW machines was decommissioned in 1971. The three intermediate pressure 34.5 MW machines were decommissioned in 1973, together with the intermediate-pressure boilers. The final 30 MW generator was decommissioned in 1978.[6]
The gross generating capability was:[6][7]
Year(s) | 1954/5 | 1955-6 | 1966-70 | 1971-72 | 1973-4 | 1975-78 |
---|---|---|---|---|---|---|
Generating capability MW | 140 | 167 | 178.75 | 176.75 | 164.25 | 60.0 |
Electricity output
Electricity output from Woolwich power station was as follows.[6][7][8][9]
Woolwich power station annual electricity output GWh.
Closure
The station closed on 30 October 1978 with a generating capacity of 57 megawatts.[10] One chimney was demolished by hand in 1978, and the remaining two by explosives in 1979. The site of the main power station building then became the Waterfront Leisure Centre car park; part of the coaling jetty remains. Around 2020 the car park was sold to Berkeley homes and it became part of the Royal Arsenal development. Ultimately the whole leisure centre will be relocated to General Gordon square.
See also
References
- ↑ "Transport for London, Thames Gateway Bridge, Appendix 12G. Gazetteer of known archaeology within 2 km study area" (PDF). Archived from the original (PDF) on 5 June 2011.
- ↑ Angus Konstam, Tony Bryan Illustrated by Tony Bryan, Tudor Warships (1): Henry VIII's Navy, Osprey Publishing, 2008, ISBN 1-84603-251-2
- 1 2 3 4 Royal Commission on the Historical Monuments of England (1995). The Power Stations of the Lower Thames. Swindon: National Monuments Record Centre.
- ↑ London County Council. London Statistics (various dates). London: London County Council.
- ↑ Mansfield, Chris. "Woolwich Power Station. A brief history". Archived from the original on 20 October 2002.
- 1 2 3 4 5 CEGB Statistical Yearbooks (various dates). CEGB, London.
- 1 2 Garrett, Frederick C., ed. (1959). Garcke's Manual of Electricity Supply. London: Electrical Press. pp. A-109, A-139.
- ↑ GEGB Annual report and accounts, various years
- ↑ Electricity Commission, Generation of Electricity in Great Britain year ended 31st December 1946. London: HMSO, 1947.
- ↑ Mr. Redmond (16 January 1984). "Coal-fired Power Stations". Parliamentary Debates (Hansard). Retrieved 1 September 2009.